Parker AC10 Inverter Error Codes: Causes and Solutions Guide

Error Code Cause Solution
LU

Under-Voltage Protection

• Input voltage is too low • Check supply voltage

• Verify parameter settings

OC

Over-current

• Acceleration time too short

• Load too heavy

• Output short circuit

• Increase acceleration time

• Check motor cables

• Check for motor overload

• Verify parameter settings

OE

DC Over-Voltage

• Input voltage too high

• Load with large inertia

• Deceleration time too short

• Check input voltage

• Add braking resistor

• Increase deceleration time

PF0

Output Phase Loss

• Motor failure

• Loose motor cable

• Inverter failure

• Check motor cables

• Inspect motor

PF1

Input Phase Loss

• Missing input phase • Check power supply

• Verify parameter settings

OL1

Inverter Overload

• Load too heavy • Reduce load

• Check drive ratio

• Use higher capacity inverter

OL2Motor Overload • Load too heavy • Reduce load

• Check drive ratio

• Use higher capacity motor

OH

Radiator Overheat

• Ambient temperature too high

• Radiator too dirty

• Cooling fan failure

• Improve ventilation

• Clean fan and radiator

OH1

PTC Overheat Protection

• External thermal protection relay is triggered • Check external thermal protection device
ESP

External Fault

• External emergency stop triggered • Check external fault device
CE

Communication Timeout Error

• Communication failure • Check communication cables

• Ensure PC/PLC sends command at fixed interval

AErr

Line Disconnected

• Analog signal cable disconnected

• Signal source damaged

• Replace signal cable

• Replace signal source

Err0

Modify Function Code Prohibited

• Cannot change parameters during operation • Modify parameters only when stopped
Err1

Wrong Password

• Wrong password entered when password protection active

• Password not entered before changing parameters

• Enter correct password
Err2

Parameter Tuning Error

• Motor not connected during auto-tuning • Connect motor properly
Err5

PID Parameter Error

• PID parameters set incorrectly • Check and correct PID settings

Contact Kỹ Thuật Việt company for repair if the issue is hardware-related.